کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
654321 885239 2007 10 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental study of thermo-hydraulic and fouling performance of enhanced heat exchangers
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Experimental study of thermo-hydraulic and fouling performance of enhanced heat exchangers
چکیده انگلیسی

The present study investigated the effect of two tube inserts (wire coil and wire mesh) on the heat transfer enhancement, pressure drop and mineral salts fouling mitigation in tube of a heat exchanger. A 3/4-in. tube that is heated by band heaters, is used which simulated a tube of heat exchanger. Working fluid is water with certain quality. The heat transfer rate averagely increased by 22–28% for wire coil (p/d = 0.125, e/d = 0.00375) and 163–174% for wire mesh (medium density) over a plain tube value, depending on type of tube insert, density of wire torsion and flow velocity. However, the pressure drop also increased substantially by 46% for wire coil and 500% for wire mesh. Wire coil insert with vibration mitigate mineral salts fouling (scaling) about 34%, and wire mesh have no effect on scaling, however it sometimes increased deposit rate.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Communications in Heat and Mass Transfer - Volume 34, Issue 7, August 2007, Pages 907–916
نویسندگان
, , ,