کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
7161145 1462849 2016 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Initial ratio optimization for the ejector cooling system with thermal pumping effect (ECSTPE)
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Initial ratio optimization for the ejector cooling system with thermal pumping effect (ECSTPE)
چکیده انگلیسی
The existing ejector cooling systems with thermal pumping effect (ECSTPEs) have severe problems of thermal energy and chilling load waste. The deviations of the initial ratio from its optimal value would lead to the deviations of the time length of cooling stage (TLCS), and finally, result in the performance deteriorations of the ECSTPEs. The results of the case study showed that, for an ECSTPE with R134a, a 10-second deviation from the optimal TLCS led to a decrease of 5.6% in the COP value and an increase of 23.7% in the chilling load, when the generation temperature, the condensing temperature and the evaporation temperature were 85 °C, 35 °C and 10 °C, respectively. Therefore, accurately controlling the TLCS corresponding to the optimal TLCS, which is derived on the basis of the optimal initial ratio, can effectively improve the performance of ECSPTEs.116
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 113, 1 April 2016, Pages 281-289