کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
7162114 1462857 2015 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental evaluation of R448A as R404A lower-GWP alternative in refrigeration systems
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Experimental evaluation of R448A as R404A lower-GWP alternative in refrigeration systems
چکیده انگلیسی
Due to the adoption of EU Regulation No 517/2014, R404A is going to be banned in Europe in most of refrigeration applications, in which is typically used, due to its very high GWP value, 3943. In this paper an experimental comparison between R404A and R448A, a non-flammable alternative with GWP of 1390, is presented. The experimental tests are intended to simulate typical freezing and conservation temperatures and different condensing conditions. Despite cooling capacity of R448A is slightly below that of R404A, R448A energy consumption is even smaller; and R448A COP is higher than that obtained using R404A. Hence, it can be concluded that R448A could be an energy efficient alternative to R404A with a GWP reduction of 70%. Compressor discharge temperature remains at non-dangerous levels.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 105, 15 November 2015, Pages 756-762