کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
730441 | 892974 | 2011 | 8 صفحه PDF | دانلود رایگان |

The automatic control of product moisture content in the paper industry is based upon online moisture measurement. Furthermore, the automatic control of other quality variables such as coat weight may also rely on the moisture measurement. The integrity of infrared radiation (IR) based online moisture measurement systems was studied by performing basic calibrations at the mills with references sealed between two glass plates. The calibrations were performed according to the EN ISO/IEC 17025 standard which is a requirement for calibration laboratories. The observed measurement errors were 2.9% moisture in the first time calibrations at the 95% confidence level. It is demonstrated that these errors can be reduced to under 0.5% moisture by applying traceable methods in the basic calibration, thus improving the integrity of online moisture measurements. Also a standardised algorithm, based on the experience from the performed calibrations, is proposed to ease the adjustment of different moisture measurement systems.
► Regular calibrations are needed to keep measurement uncertainty within specifications.
► Application of traceable calibration methods decrease basic errors efficiently.
► Decreased basic errors mean less need for manual laboratory tests.
► Standardised adjustment algorithm would ease maintenance work.
Journal: Measurement - Volume 44, Issue 10, December 2011, Pages 1937–1944