کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
761152 1462898 2012 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Modeling of existing cooling towers in ASPEN PLUS using an equilibrium stage method
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Modeling of existing cooling towers in ASPEN PLUS using an equilibrium stage method
چکیده انگلیسی

Simulation of cooling tower performance considering operating conditions away from design is typically based on the geometrical parameters provided by the cooling tower vendor, which are often unavailable or outdated. In this paper a different approach for cooling tower modeling based on equilibrium stages and Murphree efficiencies to describe heat and mass transfer is presented. This approach is validated with published data and with data collected from an industrial application. Cooling tower performance is simulated using ASPEN PLUS. Murphree stage efficiency values for the process simulator model were optimized by minimizing the squared difference between the experimental and calculated data using the Levenberg–Marquardt method. The minimization algorithm was implemented in Microsoft Excel with Visual Basic for Applications, integrated with the process simulator (ASPEN PLUS) using Aspen Simulation Workbook. The simulated cooling tower air and water outlet temperatures are in good accordance with experimental data when applying only the outlet water temperature to calibrate the model. The methodology is accurate for simulating cooling towers at different operational conditions.


► Simulation of cooling tower performance under different operating conditions.
► Cooling tower performance is simulated using ASPEN PLUS.
► Levenberg–Marquardt method used to adjust model parameters.
► Air and water outlet temperatures are in good accordance with experimental data.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 64, December 2012, Pages 473–481
نویسندگان
, , , ,