Experimental investigation of thermosyphon loop thermal performance
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Experimental investigation of thermosyphon loop thermal performance
چکیده انگلیسی


• Experimental investigations are conducted on the thermal performance of the passive loop.
• The loop fill charge ratio affected the loop start-up and showed an optimal value between 7% and 10%.
• The condenser power effect on the loop thermal performance is studied.
• The condenser jacket coolant optimal temperature and flow rate are studied.

This paper presents the experimental investigation of a two-phase closed loop. The experimental setup consists of an evaporator and a condenser connected by two insulated tubes. Using water as a working fluid, the experiments were conducted to evaluate the performance of a thermosyphon: the effects of fill charge ratio, the condenser jacket coolant inlet temperature and the mass flow rate. Finally, the results show that the optimal fill charge ratio is between 7% and 10%, the cooling system has the optimal performance when controlling the condenser jacket water temperature and flow rate at 5 °C and at 0.7 l/min respectively. System, loop, evaporator, vapor line, condenser, and liquid line thermal resistances analysis is directed additionally to the pressure and temperature evolutions for the better understand of the main parameters affecting the cooling system performance.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 84, August 2014, Pages 671–680
نویسندگان
, , , , ,