کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
764642 896995 2010 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Analysis of a combined Rankine–vapour–compression refrigeration cycle
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Analysis of a combined Rankine–vapour–compression refrigeration cycle
چکیده انگلیسی

This paper describes a theoretical analysis of a heat-powered refrigeration cycle, a combined Rankine–vapour–compression refrigeration cycle. This refrigeration cycle combines an Organic Rankine Cycle and a vapour–compression cycle. The cycle can be powered by low grade thermal energy as low as 60 °C and can produce cooling temperature as low as −10 °C. In the analysis, two combined Rankine–vapour–compression refrigeration cycles were investigated: the system with R22 and the system with R134a. Calculated COP values between 0.1 and 0.6 of both the systems were found.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 51, Issue 12, December 2010, Pages 2557–2564