کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
773022 897772 2007 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/regenerator
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/regenerator
چکیده انگلیسی

A theoretical model is developed to simulate the heat and mass transfer processes in a cross flow dehumidifier/regenerator using liquid desiccant. The model depends on NTU as input parameter, and NTU can be correlated based on the corresponding experimental data. The model is able to predict the air and desiccant parameters inside the dehumidifier/regenerator, as well as the outlet parameters, with known inlet parameters. The calculated results are compared with the experimental findings. For the total 284 groups of dehumidification experimental data with different module sizes, the average absolute discrepancies for enthalpy effectiveness and moisture effectiveness are 7.9% and 8.5%, respectively. For the 82 groups of regeneration experimental results, the average discrepancies for enthalpy and moisture effectiveness are 5.8% and 6.9%, respectively. The distributions of desiccant outlet temperatures are measured during both the dehumidification and regeneration processes, and the temperatures predicted by the theoretical model agree well with the experimental results.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 48, Issue 2, February 2007, Pages 546–554