کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
787172 1466443 2012 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental analysis of frost formation with the presence of an electric field on fin and tube evaporator
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
Experimental analysis of frost formation with the presence of an electric field on fin and tube evaporator
چکیده انگلیسی

This paper deals with an experimental study carried out to investigate the influence of DC electric fields on the performance of a fin and tube evaporator under frosting conditions. Several experiments are carried out measuring frost mass, air-side pressure drop and cooling capacity for different applied voltage, air velocity and evaporation temperature. Results show that the electric field reduces the frost mass and air-side pressure drop whereas it increases the cooling capacity. Finally, with a superimposed electric field, the overall energy consumption of the refrigerating unit reduces when referred to the same refrigerating effect.


► Frost formation on finned evaporator with electric field is experimentally studied.
► Frost mass reduction, air side pressure drop and cooling capacity are measured.
► Air side pressure drop reduction and cooling capacity increase are found.
► Overall electrical energy consumption reduces due to electric field influence.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 35, Issue 2, March 2012, Pages 468–474
نویسندگان
, , , ,