کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
789354 | 1466420 | 2014 | 9 صفحه PDF | دانلود رایگان |
• Two pre-industrial prototypes of a new NH3/LiNO3 absorption chiller were developed and experimentally characterized.
• Brazed plate heat exchangers were used in all thermal components.
• A water-cooled prototype and an air-cooled one were tested under various operating conditions.
Two pre-industrial prototypes of a new ammonia/lithium nitrate absorption chiller, a water-cooled one and an air-cooled one, have been built and experimentally characterized. The single-effect configuration of the absorption refrigeration cycle was selected for both prototypes in which brazed plate heat exchangers were used in all thermal components. These prototypes, designed for air conditioning applications, were tested under various operating conditions to assess their performance. The water-cooled prototype yields 12.9 kW of cooling capacity and an electrical COPelec of 19.3, when operating at a 15 °C chilled water temperature, 90 °C hot water temperature and a 35 °C cooling water temperature. In the case of the air-cooled prototype, at a 15 °C chilled water temperature, 90 °C hot water temperature and a 35 °C ambient air temperature, the cooling capacity is 9.3 kW and the electrical COPelec is 6.5.
Journal: International Journal of Refrigeration - Volume 45, September 2014, Pages 189–197