• A mal-distribution model is built for multi-pass condenser with vertical header.
• The model yields smaller deviations with test data than uniform distribution model.
• The effects of the aspect ratio, pass arrangement and mass flow rate are studied.
• Heat capacity varies less than 2% with varied aspect ratio or pass arrangement.
• Aspect ratio and pass arrangement clearly impact flow distribution and pressure drop.
Performance of multi-pass parallel flow condenser (MPFC) is unavoidably influenced by the refrigerant-side flow mal-distribution (MD) caused by the pressure drop in headers. Thus, a numerical MD model is proposed to predict flow distribution and performance parameters of MPFC with vertical headers and horizontal tubes. The advantage of MD model over UD model (uniform distribution model, refrigerant is assumed to be distributed into each tube evenly by ignoring the effect of header pressure drop) has been indicated by achieving better agreement with experimental data measured from variably-sized condensers A–D and data derived from a published literature. The effects of condenser aspect ratio, pass arrangement (pass number and tube number of each pass) and refrigerant mass flow rate on flow distribution, heat transfer and refrigerant-side pressure drop are investigated. The prediction results indicate that heat capacity varies much less than flow distribution and pressure drop with the change of aspect ratio or pass arrangement. Moreover, for a fixed geometry, a moderate flow rate can be searched by the MD model to obtain well flow distribution, high capacity and efficiency.
Journal: International Journal of Refrigeration - Volume 60, December 2015, Pages 234–246