This study presents theoretical investigation on the performance of air cycle refrigerator driving air conditioning system integrated desiccant system. Total system performance is evaluated and the system feasibility is examined. The system has such characteristics that (1) safe material of air and water are used as a refrigerant, (2) waste heat from air cycle refrigerator performs the regeneration of desiccant material for energy saving. It has been clarifying that (1) controlling the evaporative cooling process in air washer, the system can operate for a wide range of cooling loads, (2) the total coefficient of performance on air conditioning system is better than the conventional vapor compression system with reheating coil, and (3) the system performance highly depends on the ratio of the amount of outdoor intake air to the supply air.
Journal: International Journal of Refrigeration - Volume 29, Issue 2, March 2006, Pages 219–228