کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
854860 1470705 2015 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Energy Efficiency Measures for a High-tech Campus in California Based on Total Performance Oriented Optimization and Retrofit (TPOR) Approach
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی (عمومی)
پیش نمایش صفحه اول مقاله
Energy Efficiency Measures for a High-tech Campus in California Based on Total Performance Oriented Optimization and Retrofit (TPOR) Approach
چکیده انگلیسی

A total performance oriented optimization and retrofit (TPOR) approach is applied to evaluate the energy performance and implement the energy efficiency measures (EEMs) in a high-tech campus located in northern California, climate zone 2, with a total building area of 31,000 m2. Those EEMs identified include system optimization and retrofit on the HVAC equipment serving the office, lab and clean room area. The building energy savings were validated ac-cording to International Performance Measurement and Verification Protocol (IPMVP) utilizing the whole building energy consumption. The annual electricity usage was reduced by 3,853,625 kWh (122 kWh/m2) with a total annual energy cost savings of $304,436 (blended utility rate of $0.079/kWh). The overall simple payback was 1.6 years after incentives from the utility company. TPOR is proved to be an effective approach that can lead to a) lower costs, b) reduced project timelines, c) improved project decision making, and d) increased energy savings.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Procedia Engineering - Volume 121, 2015, Pages 75-81