کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
9708132 1466493 2005 12 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
The optimum high pressure for CO2 transcritical refrigeration systems with internal heat exchangers
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی مکانیک
پیش نمایش صفحه اول مقاله
The optimum high pressure for CO2 transcritical refrigeration systems with internal heat exchangers
چکیده انگلیسی
The system performance of a CO2 refrigeration system is greatly affected by the compressor discharge pressure. An internal heat exchanger (IHX) with high effectiveness is an important factor to achieve high system performance. The expression traditionally used to describe the heat exchange effectiveness is not suitable for CO2 systems. As a result a practical effectiveness expression for IHX, based on enthalpy difference, has been derived and is reported in this paper. Detailed analysis on the relationship between the optimum high pressure Pk,opt and other systematic parameters was performed. Evaporating temperature has little influence on Pk,opt; and IHX can minimize the sensitivity of the system to the refrigerant quality x at the evaporator outlet. Based on simulation data, a correlation of Pk,opt was developed that predicts the simulation values with a deviation of less than 3.6% in the whole range and 0.94% when the evaporating temperature t1=5.3 °C. The results reported in this paper can be used in optimum control and performance evaluation of the whole system.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Refrigeration - Volume 28, Issue 8, December 2005, Pages 1238-1249
نویسندگان
, ,