کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
1712121 | 1013119 | 2008 | 9 صفحه PDF | دانلود رایگان |

The cooling performance of a low-pressure (405 kPa working pressure) and a high-pressure fogging system (6.89 MPa) was evaluated. Experiments were conducted in two empty, naturally ventilated greenhouses under summer conditions for a period of about two months. One greenhouse was used as the treatment greenhouse (fogged house) and another was used as the control house (un-fogged house). Cooling efficiency was defined by the ratio of the temperature difference between the un-fogged and fogged greenhouses to the difference between the temperature in un-fogged house and the wet-bulb temperature in the fogged greenhouse. Evaporation efficiency was defined as the ratio of fog evaporation rate to spray rate. Cooling efficiency and evaporation efficiency were compared for the low-pressure and high-pressure systems after accounting for differences in weather conditions under which the two systems were operated. It is suggested that on average evaporation efficiency for the high-pressure system was at least 64% greater than the low-pressure system; cooling efficiency for the high-pressure system was at least 28% greater than for the low-pressure system.
Journal: Biosystems Engineering - Volume 101, Issue 1, September 2008, Pages 69–77