کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
1712155 1013121 2009 5 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Performance characteristics of a pad evaporative cooling system in a broiler house in a Mediterranean climate
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی کنترل و سیستم های مهندسی
پیش نمایش صفحه اول مقاله
Performance characteristics of a pad evaporative cooling system in a broiler house in a Mediterranean climate
چکیده انگلیسی

Temperatures in Mediterranean regions frequently exceed 30 °C for long periods during summers. Pad evaporative cooling systems may provide a solution for controlling the high temperatures that can negatively affect poultry houses. This research, aiming to investigate the performance characteristics of evaporative pad cooling systems for the Mediterranean region of Turkey, was carried out in a typical poultry house from18 July to 3 August 2006. Average evaporative cooling efficiency was determined as 69.2% on July 18, 70.1% on July 19, 69.4% on July 25, 70.8% on July 29 and 72.0% on August 3. The temperature decrease in pad exit during the experiment was determined as 6.1 °C, 7.3 °C, 4.4 °C, 5.0 °C and 5.9 °C, respectively.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Biosystems Engineering - Volume 103, Issue 1, May 2009, Pages 100–104