An absorption-compression refrigeration system driven by a mid-temperature heat source for low-temperature applications
ترجمه فارسی عنوان
یک سیستم تبرید جذب-فشرده سازی توسط یک منبع گرما در دمای متوسط ​​برای کاربردهای کم دما هدایت می شود
کلمات کلیدی
منبع گرما در دمای متوسط، کاربردهای کم دما، جذب فریزر یخچال، استفاده از آبشار، تجزیه و تحلیل ترمودینامیکی،
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
چکیده انگلیسی
An ammonia-water absorption refrigeration system is a promising way to make use of waste heat to generate cooling energy for freezing applications. When the refrigeration temperature is below −30 °C, the conventional absorption system cannot be adopted because its performance decreases dramatically. In this work, a totally heat-driven absorption-compression refrigeration system is proposed to produce cooling energy at temperatures of −40 °C to −55 °C. The proposed system comprises a heat-driven power generation subsystem using an ammonia-water mixture as the working fluid and an absorption-compression refrigeration subsystem. Simulation results showed that the coefficient of performance and the cooling capacity per unit mass of flue gas reach 0.357 and 84.18 kJ kg−1, respectively. The results of a process energy analysis showed that the cycle coupling configuration of the proposed system enhances its energy cascade utilization. Furthermore, the energy saving mechanism of the proposed system was elucidated by means of an exergy analysis and a pinch point analysis. Finally, a more comprehensive comparison with a heat-driven double-stage compression refrigeration system was conducted to show the advantage of the proposed system. This work may provide a new way to produce low-temperature cooling energy by using a mid-temperature heat source.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy - Volume 91, November 2015, Pages 215-225
نویسندگان
, , ,