کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
1742250 1521915 2015 10 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Heating and cooling performance analysis of a ground source heat pump system in Southern Germany
ترجمه فارسی عنوان
تجزیه و تحلیل عملکرد گرمایش و خنک کننده سیستم پمپ گرمایشی در جنوب آلمان
موضوعات مرتبط
مهندسی و علوم پایه علوم زمین و سیارات ژئوشیمی و پترولوژی
چکیده انگلیسی
Major findings of this work include: (1) coefficient of performance (COP) is estimated to be 3.9 for a typical winter day and energy efficiency ratio (EER) is assessed to be 8.0 for a typical summer day. These results indicate that the GSHP system has a higher efficiency for building cooling than building heating. (2) For a long-term period, the seasonal energy efficiency ratio (SEER) of the GSHP system is observed to increase by 8.7% annually, whereas the seasonal COP is decreased by 4.0% over a 4-year period. The heating and cooling performance of the GSHP system migrates in opposite trend is caused by the unevenly distributed heating and cooling load of the building. This phenomenon deserves serious attention in the design of future GSHP systems in order to avoid the reducing of energy efficiency over long-term operation.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Geothermics - Volume 53, January 2015, Pages 57-66
نویسندگان
, , , , , ,