Analytical strategies for renewable distributed generation integration considering energy loss minimization
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Analytical strategies for renewable distributed generation integration considering energy loss minimization
چکیده انگلیسی

This paper presents three alternative analytical expressions, including two new expressions, to determine the optimum sizes and operating strategy of distributed generation (DG) units considering power loss minimization and a methodology to identify the best location. These expressions can be easily adapted to consider the renewable DG units (i.e., biomass, wind and photovoltaic) for minimizing energy losses by considering time-varying demand and possible operating conditions of DG units. The results obtained on a 69-bus distribution test system demonstrate that the proposed approaches can be adequate to determine the location, size and power factor of DG unit for minimizing energy losses. The alternative expressions can be utilized depending on availability of required data and these produce similar outcomes.


► A methodology for different renewable DG allocation for energy loss minimization.
► Three alternative analytical expressions for identifying the optimum size.
► An analytical expression for calculating the optimum power factor.