کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
244228 501944 2011 6 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Simple method for estimation of effectiveness in one tube pass and one shell pass counter-flow heat exchangers
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Simple method for estimation of effectiveness in one tube pass and one shell pass counter-flow heat exchangers
چکیده انگلیسی

In one tube pass and one shell pass counter-flow heat exchangers, when both streams change temperature by different amounts, the effectiveness is defined as the temperature change for the stream with lower capacity divided by the maximum possible change and the effectiveness depends on the number of transfer units and the thermal capacity ratio. In this paper, an attempt has been made to formulate a simple-to-use method which is easier than existing approaches, less complicated and with fewer computations for accurate and rapid estimation of effectiveness in one tube pass and one shell pass counter-flow heat exchangers as a function of number of transfer units and the thermal capacity ratio. The proposed method permits estimating the exit temperature for a one tube pass and one shell pass counter-flow heat exchanger without a trial-and-error calculation. The average absolute deviations between the reported data and the proposed correlations are found to be less than 2% demonstrating the excellent performance of proposed correlation. The tool developed in this study can be of immense practical value for engineers and scientists to have a quick check on the effectiveness in one tube pass and one shell pass counter-flow heat exchangers at various conditions without opting for any experimental measurements. In particular, practice engineers would find the predictive tool to be user-friendly with transparent calculations involving no complex expressions.


► Development of a simple-to-use mathematical predictive tool.
► Estimation of effectiveness as a function of number of transfer units and the thermal capacity ratio.
► Estimating the exit temperature for one tube pass and one shell pass counter-flow heat exchangers.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Energy - Volume 88, Issue 11, November 2011, Pages 4191–4196