• A benchmarking model for the ongoing commissioning of ice rinks is proposed.
• Identification techniques of model parameters from measurements are detailed.
• Results from the benchmarking model are in good agreement with measurements.
• An application software can be implemented in the Building Energy Monitoring System.
This paper proposes the development of the benchmarking model for the ongoing commissioning of the operation of the refrigeration system of an indoor ice rink. The paper presents (1) the development of models for chillers, ice-concrete slab and controller, (2) the training phase in which the parameters of the benchmarking model are identified based on measurements under normal operating conditions, and (3) the comparison between measured and predicted energy performances. The proposed approach for the development of a benchmarking model can be implemented as application software in the Building Energy Monitoring System of any ice skating rink, if measurements of relevant independent variables are available.
Journal: Automation in Construction - Volume 35, November 2013, Pages 229–237