کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
264233 504095 2011 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
An aquifer thermal storage system in a Belgian hospital: Long-term experimental evaluation of energy and cost savings
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی های تجدید پذیر، توسعه پایدار و محیط زیست
پیش نمایش صفحه اول مقاله
An aquifer thermal storage system in a Belgian hospital: Long-term experimental evaluation of energy and cost savings
چکیده انگلیسی

Over a three years period, an aquifer thermal energy storage system was monitored in combination with a heat pump for heating and cooling of the ventilation air in a Belgian hospital. The installation was one of the first and largest ground source heat pump systems in Belgium. Groundwater flows and temperatures were monitored as well as the energy flows of the heat pumps and the energy demand of the building. The resulting energy balance of the building showed that the primary energy consumption of the heat pump system is 71% lower in comparison with a reference installation based on common gas-fired boilers and water cooling machines. This corresponds to a CO2-reduction of 1280 ton over the whole measuring period. The overall seasonal performance factor (SPF) for heating was 5.9 while the ATES system delivered cooling at an efficiency factor of 26.1. Furthermore, the economic analysis showed an annual cost reduction of k€ 54 as compared to the reference installation, resulting in a simple payback time of 8.4 years, excluding subsidies.


► Three-year monitoring campaign on an ATES installation in a Belgian hospital.
► 71% lower primary energy consumption compared to the reference installation.
► An annual energy cost reduction of k€ 54.
► A simple payback time 8.4 years exclusive subsidies.
► The ATES installation has an SPF for heating of 5.9, SPF for cooling 26.1.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy and Buildings - Volume 43, Issue 12, December 2011, Pages 3657–3665
نویسندگان
, , , , ,