Simulation and test results of low-order band harmonic filters to decrease resonance phenomenon in the KSTAR power system
کلمات کلیدی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Simulation and test results of low-order band harmonic filters to decrease resonance phenomenon in the KSTAR power system
چکیده انگلیسی


• The RPC & HF system extension was completed but the system was abnormal trip.
• We found that the reason was the expansion of non-characteristic harmonics and inter-harmonics.
• We analyzed overall harmonic resonance phenomenon to solve this problem the RPC & HF system was upgraded through low-order band harmonic filter installation.
• Harmonic resonance was sharply reduced but did not remove perfectly.
• We will try to remove harmonic resonance phenomenon.

The superconducting magnet power supply which supplies superconducting magnet coil (SC) with the power to generate plasma during a KSTAR experiment for nuclear fusion research is a nonlinear load. Characteristic harmonics are generally produced since it converts AC to DC using 6 or 12 pulsed operation. However, non-characteristic harmonics or inter-harmonics are generated according to output control characteristics. Also, 95% out of the power generated from superconducting magnet coil is reactive power. Therefore, harmonic and reactive power occurring during operation have some bad influences such as voltage drop, voltage distortion and decrease in power factor on the KSTAR power system, and reactive power compensator (RPC) & harmonic filter (HF) system which is able to compensate harmonic and reactive power at the same time was established and has been operated [1]. However, out of non-characteristic harmonics and inter-harmonics caused by output control characteristics of superconducting magnet power supply, the more compensation volume of the RPC & HF system increases, the more voltage distortion with harmonic expansion is caused by harmonics in a low-order band due to the parallel resonance in a low-order band between the KSTAR power system and the RPC & HF system. As a result, it has serious effect on the injection capacity restriction of the RPC & HF system, the unstable operation control of superconducting magnet coil, and the operation of main cooling facilities. This paper presents reasons of the resonance phenomenon of the KSTAR power system and suggests a design plan of additional facilities for stable operation of the KSTAR power system, and proves their effects through the simulation and test results.