کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
4440514 1311063 2010 5 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Assessment of airborne environmental bacteria and related factors in 25 underground railway stations in Seoul, Korea
موضوعات مرتبط
مهندسی و علوم پایه علوم زمین و سیارات علم هواشناسی
پیش نمایش صفحه اول مقاله
Assessment of airborne environmental bacteria and related factors in 25 underground railway stations in Seoul, Korea
چکیده انگلیسی

This study assessed bacterial concentrations in indoor air at 25 underground railway stations in Seoul, Korea, and investigated various related factors including the presence of platform screen doors (PSD), depth of the station, year of construction, temperature, relative humidity, and number of passengers. A total of 72 aerosol samples were collected from all the stations. Concentrations of total airborne bacteria (TAB) ranged from not detected (ND) to 4997 CFU m−3, with an overall geometric mean (GM) of 191 CFU m−3. Airborne bacteria were detected at 23 stations (92%) and Gram-negative bacteria (GNB) were detected at two stations (8%). TAB concentrations of four stations (16%) exceeded 800 CFU m−3, the Korea indoor bio-aerosol guideline. The results of the study showed that TAB concentrations at the stations without PSD showed higher TAB concentrations than those with PSD, though not at statistically significant levels. TAB concentrations of deeper stations revealed significantly higher levels than those of shallower stations. Based on this study, it is recommended that mitigation measures be applied to improve the indoor air quality (IAQ) of underground railway stations in Seoul, with focused attention on deeper stations.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Atmospheric Environment - Volume 44, Issue 13, April 2010, Pages 1658–1662
نویسندگان
, , , , ,