کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
5002588 1368455 2016 7 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Rogowski Electronic Transformer Performance Evaluation and Its Impact on PMUs
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مکانیک محاسباتی
پیش نمایش صفحه اول مقاله
Rogowski Electronic Transformer Performance Evaluation and Its Impact on PMUs
چکیده انگلیسی
As an important component of process level in the smart substation, the electronic transformer is fundamental for the monitoring and control of the smart grid. In this paper, the transformation characteristics of the Rogowski electronic transformer under both static and dynamic conditions, as well as its impact on Phasor measurement units (PMUs), are studied by the theoretical analysis, simulations, and experiments. It can be concluded that the electronic transformer has a good amplitude and frequency response, and it can track the static and dynamic phasor. However, the DC offset and the harmonic components brought by the electronic transformer affect the frequency and the rate of the change of the frequency estimations performed by PMUs.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: IFAC-PapersOnLine - Volume 49, Issue 27, 2016, Pages 96-102