کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
585114 877906 2006 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Levels of polychlorinated biphenyls (PCBs) in transformer oils from Korea
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی بهداشت و امنیت شیمی
پیش نمایش صفحه اول مقاله
Levels of polychlorinated biphenyls (PCBs) in transformer oils from Korea
چکیده انگلیسی
Using Korean waste official method, polychlorinated biphenyls (PCBs) were analyzed from 33 transformer oils collected under National Institute of Environmental Research (NIER) in Republic of Korea (ROK) and their emission rate in Korea was estimated. Practical quantification limits analyzed by this method were in the ranges of 0.02 and 0.05 mg L−1, and recovery of samples was in the ranges of 77-97%. The analytical results showed that PCBs in the transformer oils were identified as Aroclor 1242, 1254 or 1260. Twenty-nine samples were determined to contain PCBs of >0.05 mg L−1 and among these samples, nine samples contained to have >2 mg kg−1 which is limit of Waste Control Act (WCA) with regard to PCBs in transformer oil from Korea. The concentrations of PCBs in transformer oils were between N.D. (not detected) and 48.33 mg kg−1. PCBs concentrations did not exceed 50 mg kg−1 which is generally accepted limit for the definition of waste in POPs Guideline of Basel Convention.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Journal of Hazardous Materials - Volume 137, Issue 3, 11 October 2006, Pages 1514-1522