کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
622259 1455177 2010 12 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
MINLP optimization of mechanical draft counter flow wet-cooling towers
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی تصفیه و جداسازی
پیش نمایش صفحه اول مقاله
MINLP optimization of mechanical draft counter flow wet-cooling towers
چکیده انگلیسی

In this paper, the problem of the optimal design of mechanical draft counter flow cooling towers that meets a set of specified constraints is formulated as a mixed-integer nonlinear programming (MINLP) problem. The Merkel's method is used to specify the characteristic dimensions of cooling towers, together with empirical correlations for the loss and overall mass transfer coefficients in the packing region of the tower. Water-to-air mass ratio, water mass flow rate, water inlet and outlet temperatures, operational temperature approach, type of packing, type of draft, height and area of the tower packing, total pressure drop of air flow, power consumption of the fan, and water consumption provide the set of optimization variables. The MINLP problem is formulated so as to minimize the total annual cost of the cooling tower. The performance of the proposed procedure is shown with the solution of six examples.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Chemical Engineering Research and Design - Volume 88, Issues 5–6, May–June 2010, Pages 614–625
نویسندگان
, , ,