کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
654369 885241 2010 12 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental investigation of twisted tape inserts performance on condensation heat transfer enhancement and pressure drop
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Experimental investigation of twisted tape inserts performance on condensation heat transfer enhancement and pressure drop
چکیده انگلیسی
A comprehensive experimental investigation is conducted on the augmentation of heat transfer coefficients and pressure drop during condensation of HFC-134a in a horizontal tube at the presence of different twisted tape inserts. The test section is a 1.04 m long double-tube counter-flow heat exchanger. The refrigerant flows in the inner copper and the cooling water flows in annulus. The experiments are performed for a plain tube and four tubes with twisted tapes inserts of 6, 9, 12 and 15 twist ratios. The pressure drop is directly measured by a differential pressure transducer. It is found that the twisted tape with twist ratio of 6 gives the highest enhancement in the heat transfer coefficient and the maximum pressure drop compared to the plain tube on a nominal area basis. For this case the enhancement in heat transfer and the pressure drop are increased by 40 and 240% in comparison with to the plain tube. It is observed that the twisted tape with the twist ratio of 9 has the best performance enhancing the heat transfer with the minimum pressure drop. Also empirical correlations are developed to predict smooth tube and swirl flow pressure drop. Predicted results are compared to experimental data and it is found that these correlations are reliable for pressure drop estimation.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Communications in Heat and Mass Transfer - Volume 37, Issue 9, November 2010, Pages 1376-1387
نویسندگان
, , ,