چکیده انگلیسی
The transient overvoltages associated to the interruption of high direct currents with high current derivative, at the base of the operation of a Quench Protection System for Superconducting Coils, have been studied, with particular reference to the JT-60SA project, which adopt edge technology solutions for current interruption: a Hybrid mechanical-static Circuit Breaker as main circuit breaker in series with a PyroBreaker as backup protection. The paper reports in particular on the analyses of the intervention of the backup circuit breaker in the final circuital conditions, considering the actual power connections that will be implemented on Site. The key elements which influence the peak value of the voltage and the relation existing among the different stray impedances of the circuit are identified, thus giving general guidelines for the design of the layout of the power connections. The specific case of JT-60SA is considered, but general criteria can be derived.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Fusion Engineering and Design - Volumes 98–99, October 2015, Pages 1109-1112