کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
6750207 509119 2015 56 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
A case study: The energy performance gap of the Center for Interactive Research on Sustainability at the University of British Columbia
ترجمه فارسی عنوان
یک مطالعه مورد: شکاف عملکرد انرژی مرکز تحقیقات تعاملی در زمینه پایداری در دانشگاه بریتیش کلمبیا
کلمات کلیدی
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی عمران و سازه
چکیده انگلیسی
The present paper shows that in the case of the CIRS building the major sources of the performance gap are that the building has been built and is operated differently from what was expected. A major component of the CIRS energy concept is heat exchange with a neighboring building; however, because of design and commissioning deficits, the heat exchange falls short of the design intent. Furthermore, a waste water treatment plant located in the building is on the building's meters and included in the measured data, but not in the energy model. The transformers' electricity consumption was not in the energy model either and they were significantly inefficient. Part of the building's unanticipated usage is large lighting and plug loads.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Journal of Building Engineering - Volume 4, December 2015, Pages 127-139
نویسندگان
, , , , ,