New coordination approach to minimize the number of re-adjusted relays when adding DGs in interconnected power systems with a minimum value of fault current limiter
موضوعات مرتبط
مهندسی و علوم پایه مهندسی کامپیوتر هوش مصنوعی
پیش نمایش صفحه اول مقاله
New coordination approach to minimize the number of re-adjusted relays when adding DGs in interconnected power systems with a minimum value of fault current limiter
چکیده انگلیسی
The proposed approach is implemented and effectively tested on the large well-known interconnected IEEE-39 bus test system with 84 relays. Its results are compared with other approaches where, no re-adjusted relays settings are applied. A noteworthy advantage of the proposed scheme is the ability to implement a reduced FCL value than the critical value, by adjusting only one relay settings in the whole network. The proposed scheme may also be extended to re-adjust settings of more than one relay and get further reduced value of FCL. Furthermore, it is also shown that a more optimum value of the total operating time of all primary relays for near end faults is achieved when applying the proposed method rather than other traditional schemes.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Electrical Power & Energy Systems - Volume 85, February 2017, Pages 32-41