کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
704416 891253 2006 5 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Maclaurin-Newton algorithms in 132 kV subtransmission security simulations
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Maclaurin-Newton algorithms in 132 kV subtransmission security simulations
چکیده انگلیسی
This paper examines how applicable approximate Jacobian inversions are when implemented in the security analysis simulations of 132 kV power subtransmission. The complete Scottish 400/275/132 kV power transmission network was simulated, including the 132 kV subtransmission network with its high r/x ratios. Both the coupled and decoupled Maclaurin-Newton load flow algorithms were tested. It was proved that high r/x ratios found in the 132 kV level, five times higher than in 400/275 kV, have an important influence on convergence and accuracy of the inversion Jacobian load flow algorithms. It was found that the decoupled inversion load flow was applicable for 132 kV, it converged regularly, but had worse convergence and accuracy characteristics, compared to 400/275 kV applications, while the coupled inversion load flow was not applicable at all for 132 kV, it always diverged.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Electric Power Systems Research - Volume 76, Issue 12, August 2006, Pages 1084-1088