کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
705023 1460928 2012 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
High frequency earthing impedance measurements at Camp Blanding, Florida
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
High frequency earthing impedance measurements at Camp Blanding, Florida
چکیده انگلیسی

This paper discusses the results of high frequency earthing impedance measurements made on the earthing systems installed at Camp Blanding, Florida. Much of the initial information used to confirm the results obtained from high frequency earthing impedance testers is based on comparison of measured data from specifically designed earthing systems with simulations of the expected response of the grounding system. More recently, testing using devices injecting a surge current into a grounding system was compared with earthing impedance testers measuring selected frequencies of up to 1 MHz. It was found that these devices yielded similar results. The impedance measurements at Camp Blanding were compared with currents measured during triggered lightning testing conducted in 2004 and 2005. Even though the dry porous sand at the site made the measurements difficult and the earthing impedance measurements were made four years and longer after system installation and current measurements, correlation was also found between the measured impedance and the measured current distribution.


► Performance of high frequency measurements at Camp Blanding lightning earthing system.
► Data obtained at high frequency in spite of bad soil when low frequency unable to give reading.
► Sharing of current consistent between measurements and lightning standard formulas.
► Sharing of current consistent between measurements and triggerred lightning data.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Electric Power Systems Research - Volume 85, April 2012, Pages 50–58
نویسندگان
, , ,