کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
706013 | 891393 | 2006 | 8 صفحه PDF | دانلود رایگان |

This paper reports the case of some EHV circuit-breaker repetitive failures during the opening of a 100 MVAR shunt reactor in a 400 kV substation in central part of Iran. By taking advantage of the simulation capabilities of EMTP-RV, the restructured version of the DCG-EMTP and its new GUI, major understanding of arc-circuit interaction phenomena was achieved. Simulation results show without any doubt that opposite-polarity high frequency arc-instability-dependant oscillations caused mainly by current transformers on each side of the breaker were responsible for its thermal failures and thus the non-interruption of the low 50 Hz reactor current by the 50 kA circuit-breaker.This paper represents a major contribution to the field of shunt reactor circuit-breaker applications. It is expected that transient simulations with EMTP-RV incorporating circuit parameters frequency-dependency and dynamic arc modeling, will contribute, in some cases, to a much safer shunt reactor installation.
Journal: Electric Power Systems Research - Volume 76, Issue 8, May 2006, Pages 655–662