کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
706013 891393 2006 8 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Potential risk of failures in switching EHV shunt reactors in a one-and-a-half breaker scheme
کلمات کلیدی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی مهندسی انرژی و فناوری های برق
پیش نمایش صفحه اول مقاله
Potential risk of failures in switching EHV shunt reactors in a one-and-a-half breaker scheme
چکیده انگلیسی

This paper reports the case of some EHV circuit-breaker repetitive failures during the opening of a 100 MVAR shunt reactor in a 400 kV substation in central part of Iran. By taking advantage of the simulation capabilities of EMTP-RV, the restructured version of the DCG-EMTP and its new GUI, major understanding of arc-circuit interaction phenomena was achieved. Simulation results show without any doubt that opposite-polarity high frequency arc-instability-dependant oscillations caused mainly by current transformers on each side of the breaker were responsible for its thermal failures and thus the non-interruption of the low 50 Hz reactor current by the 50 kA circuit-breaker.This paper represents a major contribution to the field of shunt reactor circuit-breaker applications. It is expected that transient simulations with EMTP-RV incorporating circuit parameters frequency-dependency and dynamic arc modeling, will contribute, in some cases, to a much safer shunt reactor installation.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Electric Power Systems Research - Volume 76, Issue 8, May 2006, Pages 655–662
نویسندگان
, , , ,