کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
759428 | 1462626 | 2009 | 9 صفحه PDF | دانلود رایگان |

This paper investigates the transient heat and mass transfer in liquid desiccant air-conditioning process at low flow conditions. Using local volumetric average approach, one-dimensional non-equilibrium heat and mass transfer models are developed to describe the humid air and liquid desiccant interaction at counter flow configuration. Using triethylene glycol solution as desiccant, some experimental studies are completed. Experimental results are used to justify the numerical models. Numerical results are then obtained to demonstrate process characteristics. The models include a transient desiccant flow model for initial liquid desiccant building-up process, empirical wetted specific surface ratio for mass transfer, and heat and mass transfer coefficients. The objective of this research is to develop a process analytical tool for liquid desiccant air-conditioner design.
Journal: Communications in Nonlinear Science and Numerical Simulation - Volume 14, Issues 9–10, September–October 2009, Pages 3599–3607