کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
764571 896990 2011 6 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
On the pressure drop in Plate Heat Exchangers used as desorbers in absorption chillers
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
On the pressure drop in Plate Heat Exchangers used as desorbers in absorption chillers
چکیده انگلیسی

The influence of the pressure drop in Plate Heat Exchangers (PHE) in the boiling temperature of LiBr–H2O and NH3–H2O solutions is studied. For the NH3–H2O solution, the pressure drop-temperature saturation relationship estates that high pressure drops can be allowed in the solution with negligible changes in the saturation temperature, and in the PHE performance. Besides, in the case of the LiBr–H2O solution, as the working pressure is usually very low, the analysis of the pressure drop must be taken as a main limiting parameter for the use of Plate Heat Exchangers as vapour generators. In this case, the pressure drop may considerably change the boiling temperature of the solution entering the heat exchanger and therefore a higher heating fluid temperature may be required. A guideline to design these systems is proposed.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 52, Issue 2, February 2011, Pages 1520–1525
نویسندگان
, , , ,