کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
766535 897106 2007 10 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Detection and diagnosis for sensor fault in HVAC systems
موضوعات مرتبط
مهندسی و علوم پایه مهندسی انرژی انرژی (عمومی)
پیش نمایش صفحه اول مقاله
Detection and diagnosis for sensor fault in HVAC systems
چکیده انگلیسی

Principal component analysis (PCA) is presented to detect single sensor faults in heating, ventilation and air conditioning (HVAC) systems. Three PCA models, based on energy balance and air side and water side flow pressure balances, respectively, are set up to detect whether there is any abnormality occurring in the systems. With any fault discovered, a joint angle plot, which compares the new fault vector with known ones in the library, can be used to isolate the faulty sensor indeed. As pre-diagnosis, some expert rules are used to improve the diagnosing process. With the strategy of joint angle plot combined with expert rules, the single sensor fault can be timely isolated on line.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Energy Conversion and Management - Volume 48, Issue 3, March 2007, Pages 693–702