کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
10391765 885003 2011 6 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Rheology and flow characteristic of urban untreated sewage for cooling and heating source
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Rheology and flow characteristic of urban untreated sewage for cooling and heating source
چکیده انگلیسی
Urban untreated sewage is a kind of excellent cooling and heating source. The rheology and flow characteristic of sewage is the basis of the application of sewage cooling and heating source system. They are studied based on the theoretical assumption of single flow model, principle of tube-type rheometer, and field experiments. The rheological basic equations and flow characteristic of urban untreated sewage are developed. The results of research indicate that sewage has the characteristic of non-Newtonian power-law. The rheological basic equation is τ=0.0031γ˙0.92. The distance coefficient of drag in turbulence of sewage in circle pipe is λt = 0.186(Re′)−0.208. The equations of velocity distribution of sewage are, respectively, v+ = 2.5 ln y+ + 5.7, v+ = 5.11 ln y+ − 3.22, and v+ = y+ in turbulence, intermediate, and laminar current zone in circle pipe. Those can be used to instruct engineering application, design, analysis, and farther research of the system.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Experimental Thermal and Fluid Science - Volume 35, Issue 4, May 2011, Pages 612-617
نویسندگان
, , , ,