Characterization of a dual taper thermosiphon loop for CPU cooling in data centers
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Characterization of a dual taper thermosiphon loop for CPU cooling in data centers
چکیده انگلیسی
The inefficient cooling processes in data centers consume a large amount of energy making them very expensive. This study is focuses on using a thermosiphon loop as an efficient replacement of currently used air cooling and water cooling techniques for dissipating large heat loads from the CPUs. A symmetric dual taper configuration is introduced in the evaporator to generate a highly efficient and stable two-phase flow in the system using HFE7000. Three different taper angles in the evaporator - 2°, 2.5°, and 3° - are studied, and the respective heat transfer performances are evaluated. The evaporator has 200 µm square microchannels machined on a 34.5 mm × 32 mm copper heat sink. Prior to CPU testing, the dual taper evaporator performance is evaluated in a benchtop thermosiphon loop in which the evaporator is heated by electric heaters. The loop is able to dissipate 280 W without reaching the critical flux point with a heat transfer coefficient of 26 kW/m2 °C. The thermosiphon loop is then tested for cooling a data center server with an i7-930 processor with thermal design power (TDP) of 130 W. The cooling performance of the thermosiphon loop is compared with commercial air based and water based coolers in both server and benchtop configurations.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 146, 5 January 2019, Pages 450-458
نویسندگان
, ,