کد مقاله | کد نشریه | سال انتشار | مقاله انگلیسی | نسخه تمام متن |
---|---|---|---|---|
1818207 | 1525725 | 2013 | 7 صفحه PDF | دانلود رایگان |

This paper proposes the combination of a load frequency control (LFC) with superconducting magnetic energy storage (SMES) to solve the LFC problem in interconnected power systems. By using this combination, the speed damping of frequency and tie-line power flow deviations is considerably increased. A new control strategy of SMES is proposed in this paper. The problem of determining optimal parameters of PID and SMES control loop is considered as an optimization problem and a pattern search algorithm (PS) optimization is employed to solve it. The simulation results show that if an SMES unit is installed in an interconnected power system, in addition to eliminating oscillations and deviations, the settling time in the frequency and tie-line power flow responses is considerably reduced.
► Load frequency control of PID type is combined with a SMES.
► Damping speed of frequency and tie-line power flow deviations are considerably increased.
► Optimal parameters of PID and SMES control loop are obtained by PS optimization.
Journal: Physica C: Superconductivity - Volume 487, 15 April 2013, Pages 60–66