Smoke concentrations inside and outside of a corridor-like enclosure
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی عمران و سازه
پیش نمایش صفحه اول مقاله
Smoke concentrations inside and outside of a corridor-like enclosure
چکیده انگلیسی


• Smoke measurements conducted inside a corridor-like enclosure together with measurements outside in an exhaust duct.
• Smoke volume fraction is governed by the global equivalence ratio, the temperatures and residence time inside the enclosure.
• Reversed gas flows were observed behind the flames inside the corridor.

This work presents smoke measurements and correlations inside and outside of a corridor-like enclosure fires in order to determine the effects of burning on smoke concentrations inside and outside the enclosure. Thirty eight experiments were performed in a three metre long corridor-like enclosure having a cross section 0.5 m×0.5 m, door like openings in the front panel and a gaseous burner located near the closed end. Smoke concentrations were measured at two locations inside the enclosure and also in the exhaust duct of a hood collecting the fire gases from the enclosure. It was found that smoke concentration in the exhaust duct decreased whereas smoke concentration inside the enclosure increased after the flames started moving towards the opening and external burning occurred. This increased smoke concentration inside the enclosure was caused by reversion of the flow pattern inside the enclosure after the flames moved past a point towards the opening. Namely, the flow pattern changed direction behind the flame front in the sense that hot gases in the upper layer were travelling backwards towards the closed end of the corridor thus contributing to smoke increase inside the enclosure. This change of flow pattern was confirmed in all experiments by bidirectional probe velocity measurements in the upper and lower layer as well as by oxygen concentrations and temperature measurements inside the enclosure. These results are useful for CFD validation and specifically applicable for assessing smoke hazards in corridor fires in buildings where smoke concentrations can be much larger than anticipated owing to leakage to adjacent rooms behind a moving flame front.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Fire Safety Journal - Volume 60, August 2013, Pages 37–45