Suppression of sodium fires with liquid nitrogen
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی عمران و سازه
پیش نمایش صفحه اول مقاله
Suppression of sodium fires with liquid nitrogen
چکیده انگلیسی

Sodium has unusual fire hazards, including autoignition when heated in air or exposed to liquid water. Owing to limitations of existing suppression agents for sodium pool fires, suppression using liquid nitrogen (LN2) is examined here. Sodium pools of 5–80 g were heated in stainless steel beakers. At about 290 °C, pool surface autoignition occurred and caused a rapid pool temperature increase. Vapor phase combustion occurred when the pools reached 320–450 °C, ultimately leading to pool temperatures up to 700 °C. For suppression tests, LN2 delivery (at 2.7 g/s) began when the fires became fully-developed, near a pool temperature of 600 °C. Liquid nitrogen was found to be an effective suppression agent. The minimum amount of LN2 required to suppress a fully-developed sodium pool fire was found to be about three times the initial sodium pool mass.


► Sodium pool fires of 5–80 g are observed.
► Liquid nitrogen is demonstrated to suppress liquid fires.
► Suppression requires, by mass, at least three times as much liquid nitrogen as sodium.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Fire Safety Journal - Volume 58, May 2013, Pages 204–207