کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
270543 504768 2007 13 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental study of natural roof ventilation in full-scale enclosure fire tests in a small compartment
موضوعات مرتبط
مهندسی و علوم پایه سایر رشته های مهندسی مهندسی عمران و سازه
پیش نمایش صفحه اول مقاله
Experimental study of natural roof ventilation in full-scale enclosure fire tests in a small compartment
چکیده انگلیسی

An analysis of full-scale fire test experimental data is presented for a small compartment (3×3.6×2.3 m). A square steady fire source is placed in the center of the compartment. There is an open door and a horizontal opening in the roof, so that natural ventilation is established for the well-ventilated fire. A parameter study is performed, covering a range of total fire heat release rates (330, 440 and 550 kW), fire source areas (0.3×0.3 m and 0.6×0.6 m) and roof ventilation opening areas (1.45×1 m, 0.75×1 m and 0.5×1 m). The impact of the different parameters is examined on the smoke layer depth and the temperature variations in vertical direction in the compartment. Both mean temperatures and temperature fluctuations are reported. The total fire heat release rate value has the strongest influence on the hot smoke layer average temperature rise, while the influence of the fire source area and the roof opening is smaller. The hot smoke layer depth, determined from the measured temperature profiles, is primarily influenced by the fire source area, while the total fire heat release rate and the roof opening only have a small impact. Correlations are given for the hot smoke layer average temperature rise, the buoyancy reference velocity and the total smoke mass flow rate out of the compartment, as a function of the different parameters mentioned. Based on the experimental findings, it is discussed that different manual calculation methods, widely used for natural ventilation design of compartments in the case of fire, under-predict the hot layer thickness and total smoke mass flow rate, while the hot layer average temperature is over-estimated.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Fire Safety Journal - Volume 42, Issue 8, November 2007, Pages 523–535
نویسندگان
, ,