کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
276224 1429545 2013 4 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Field experimental study on the cooling effect of mine cooling system acquiring cold source from return air
موضوعات مرتبط
مهندسی و علوم پایه علوم زمین و سیارات زمین شناسی اقتصادی
پیش نمایش صفحه اول مقاله
Field experimental study on the cooling effect of mine cooling system acquiring cold source from return air
چکیده انگلیسی

With the increase of mining depth, more and deeper coal mines are limited by heat disaster. The cooling energy in deep mine cooling system comes from mine water inrush or ground cooling tower, but we cannot adopt the two methods because mine water inrush in many old coal mines in China is limited. What is more, the cooling pipelines cannot be put in narrow pit-shaft. To settle the problem above, according to the characteristics of Zhangxiaolou Coal Mine, this paper adopts the deep mine return air as the cooling energy for deep mine cooling system. In addition, we carried out cite test to extract cold energy from return air. Through monitoring the water quantity, water temperature of cooling system and air temperature, we got the thermodynamic equilibrium parameters during the cooling energy acquisition analysis and the effect of cooling system that the temperature and humidity on working face are respectively reduced to 8–12 °C and 8–15% through cooling. This research offers experimental reference for deep mine cooling which lacks cooling energy.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: International Journal of Mining Science and Technology - Volume 23, Issue 3, May 2013, Pages 453–456
نویسندگان
, ,