کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
4990332 1457100 2018 23 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Improvement of energy parameters using R442A and R453A in a refrigeration system operating with R404A
کلمات کلیدی
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Improvement of energy parameters using R442A and R453A in a refrigeration system operating with R404A
چکیده انگلیسی
In this study, R404A having high GWP (global warming potential) was experimentally compared with R442A and R453A refrigerants which have low GWP. The alternatives refrigerants of R442A and R453A were directly tested without performing a constructional modification in the refrigeration system. Three different evaporation temperature (−6, −3 and 0 °C) and three condenser temperature (35, 40, 45 °C) cases were investigated in the experimental work. Power consumption of compressor was highest for R404A while it was the lowest for R453A at three condenser temperatures. The measurements presented that cooling capacity amounts of R442A and R453A were greater by 1-8% than that of R404A. In comparison with R404A, COP (coefficient of performance) value was better by 5-12% using R442A and it was substantially improved by about 10-14% for the case of R453A refrigerant. The volumetric efficiency values were obtained as the highest for R453A at the covered experimental cases. The mass flow rate and quality of refrigerant at evaporator inlet were also reduced as a result of using considered alternatives refrigerants.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 129, 25 January 2018, Pages 243-249
نویسندگان
, , ,