Experimental investigations on performance of liquid desiccant-vapor compression hybrid air conditioner
ترجمه فارسی عنوان
تحقیقات تجربی در مورد عملکرد تهویه مطبوع هیبرید کمپرسور بخار مایع
کلمات کلیدی
ستون جذب کننده و بازسازنده همراه، تحقیقات تجربی، سیستم تهویه مطبوع هیبریدی، مایع خشک کن، سیستم فشرده سازی بخار
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
چکیده انگلیسی


• A liquid desiccant vapor compression hybrid system is fabricated and tested.
• The liquid desiccant reduces latent load but equally increases sensible load.
• Hybrid system performance is studied for varying room temperature and humidity.
• Higher room temperature lowers air dehumidification and desiccant regeneration.
• Increase of room specific humidity enhances dehumidification and also regeneration.

A coupled desiccant column is integrated with a conventional room air conditioner (AC) to enhance dehumidification of the room air. One desiccant column (absorber) is placed after the evaporator the other (regenerator) after the condenser of the AC unit. Such a novel liquid desiccant vapour compression hybrid air conditioning system has been fabricated and tested in a balanced ambient room type calorimeter for very low flow rates of liquid desiccant (lithium bromide solution). The moisture from the cold supply air is transferred to the hot condenser air by the desiccant flowing in the loop, thereby complimenting the dehumidification of the room air at the evaporator. The supply air is also sensibly heated during the dehumidification process by liquid desiccant in the absorber, which together enables the hybrid system to maintain low humidity in the room. Whereas the liquid desiccant is regenerated by the condenser waste heat, the entire cooling is derived only by the AC unit. The experimental results show that an increase of room temperature reduces both dehumidification of process air and regeneration of liquid desiccant, whereas an increase of room specific humidity enhances both these for the flow rate of the liquid desiccant in the range of 0.2–1.6% of the air flow rate through the absorber.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 77, 25 February 2015, Pages 153–162