کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
647312 1457178 2012 9 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Impact of district heating and groundwater heat pump systems on the primary energy needs in urban areas
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Impact of district heating and groundwater heat pump systems on the primary energy needs in urban areas
چکیده انگلیسی

This work is focused on the planning of rational heating systems for urban areas.From the sustainability viewpoint, district heating is an important option to supply heat to the users in urban areas. The energy convenience of such option depends on the annual energy request, the population density and the efficiency in heat production. Among the alternative technologies, geothermal heat pumps (both open loop and closed loop heat pumps) play a crucial role.This paper aims to propose a procedure to select which users in an urban area should be connected with a district heating network and which ones should be heated through an alternative technology, in order to reach a globally optimal system from the energy viewpoint.The procedure proposes district heating as the initial choice for all the users. The users are then progressively disconnected to the network, according with the primary energy required to supply them heat, and the alternative technology is considered for disconnected users. Here, ground water heat pump is considered as the alternative technology. The total primary energy request is assumed as the objective function to be minimized. To reach this result, the exergetic cost of heat supplied through heat pumps system must be evaluated. Such evaluation is not trivial, as it must include proper analysis of both the district heating network and the alternative system. In the case of densely populated areas, an additional consideration is necessary: the subsurface thermal degradation caused by heat pump installations may affect the performances of surrounding installations. This impact is calculated through a thermo-fluid dynamic model of the subsurface.The application to an Italian town is considered as a test case. The optimal configuration of the overall urban heating system is obtained. This configuration corresponds to the minimum primary energy request to supply heat to all the users (those connected to the network and those using an alternative heating system).


► Planning of urban heating systems based on DH and groundwater heat pumps.
► Performance evaluation of multiple groundwater heat pump installations through CFD.
► Thermoeconomic based approach for optimal system configuration.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 40, July 2012, Pages 18–26
نویسندگان
, , , ,