Drop size distribution below different wet-cooling tower fills
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Drop size distribution below different wet-cooling tower fills
چکیده انگلیسی

Drop size distribution is measured photographically below three different counter-flow wet-cooling tower fills (cross-fluted film, trickle and fibre cement) and a number of splash grid configurations installed below a trickle fill. The air and water flow rates are varied to investigate their influence on drop size. The data for each test case is presented as a cumulative mass distribution curve, Sauter mean diameter, Rosin–Rammler distribution curve and Rosin–Rammler function. The main objectives are to describe the implemented experimental apparatus and measurement techniques and to determine the drop size distribution beneath different fills and ultimately the drop size reduction capability of grids installed below the fill. An important conclusion is that the Rosin–Rammler distribution curve generally does not fit the measured data adequately and thus should be avoided.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 29, Issues 8–9, June 2009, Pages 1552–1560