Modelling and analysis of air-cooled reciprocating chiller and demand energy savings using passive cooling
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Modelling and analysis of air-cooled reciprocating chiller and demand energy savings using passive cooling
چکیده انگلیسی
The study presents modelling and analysis of air-cooled chiller system in an office building at Central Queensland University in Rockhampton, Australia. EnergyPlus, building energy simulation software, has been used to model and to simulate the energy savings. Base case cooling energy has been compared with measured data. The simulated results show a reasonable agreement with the measured data. As a passive cooling means, the effect of economiser usages and pre-cooling have been simulated and analysed to assess annual demand savings for an energy intensive office building at Rockhampton, Australia. It was found that implementation of the pre-cooling and economiser system could save 115 kW/m2/month and 72 kW/m2/month total cooling energy and 26 kW/m2/month and 42 kW/m2/month chiller energy, respectively.
ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 29, Issues 8–9, June 2009, Pages 1825-1830