کد مقاله کد نشریه سال انتشار مقاله انگلیسی نسخه تمام متن
648988 884639 2007 5 صفحه PDF دانلود رایگان
عنوان انگلیسی مقاله ISI
Experimental study of a solid adsorption cooling system using flat-tube heat exchangers as adsorption bed
موضوعات مرتبط
مهندسی و علوم پایه مهندسی شیمی جریان سیال و فرایندهای انتقال
پیش نمایش صفحه اول مقاله
Experimental study of a solid adsorption cooling system using flat-tube heat exchangers as adsorption bed
چکیده انگلیسی

In this paper, a solid adsorption cooling system with silica gel as the adsorbent and water as the adsorbate was experimentally studied. To reduce the manufacturing costs and simplify the construction of the adsorption chiller, a vacuum tank was designed to contain the adsorption bed and evaporator/condenser. Flat-tube type heat exchangers were used for adsorption beds in order to increase the heat transfer area and improve the heat transfer ability between the adsorbent and heat exchanger fins. Under the standard test conditions of 80 °C hot water, 30 °C cooling water, and 14 °C chilled water inlet temperatures, a cooling power of 4.3 kW and a coefficient of performance (COP) for cooling of 0.45 can be achieved. It has provided a specific cooling power (SCP) of about 176 W/(kg adsorbent). With lower hot water flow rates, a higher COP of 0.53 can be achieved.

ناشر
Database: Elsevier - ScienceDirect (ساینس دایرکت)
Journal: Applied Thermal Engineering - Volume 27, Issue 13, September 2007, Pages 2195–2199
نویسندگان
, , ,